|
PERFORMANCE
IN CASE OF ELECTRICAL ACCIDENTS:
- To
cut the electrical current.
-
To cause a short circuit.
-
Isolated of the side of the electrical current and the earth side, to separate
the victim of the conductor.
-
To begin the resuscitation (mouth to mouth and cardiac massage), trying that the
time of performance is the minimum since when takes more in reacting less
possibilities of saving the victim will have

The
reanimation must be made as rapidly as possible so that the victim can react
NORMS OF
SECURITY BEFORE ELECTRICAL RISK
1 -
MAJORITIES:
-
Electrical systems of low tension are considered those in which the nominal
tensions are inferior to 1000V.
-
Before initiating works in low tension it will be come to identify the conductor
or electrical system where it must work.
-
All electrical system will be considered low tension while the opposite with
apparatuses does not demonstrate itself destined to the effect.
-
Metallic stairs for works with tension are not due to use.

Electrical
works are not due to make in places where there is stored material inflammable.
-
Works with tension are not due to make in the premises where material
inflammable explosives exist or.
-
The works in electrical systems of low tension in those cases that by proximity
or cross other facilities can make contact accidentally with enemy with these,
or will eliminate the possibility of contact by means of screens, grates, etc..,
or will have to become disconnected and to ground in short circuit and the
installation of low tension.
-
In the premises humid, wet or of atmosphere explosive the devices of maneuver of
low tension they must be driven being placed the worker on a platform of
isolated material, which does not have to keep in the premises of the
characteristics before mentioned.

All electrical
work must be made fulfilling the security norms.
-
To replace fuses in an electrical system of low tension whenever it is possible
it will let the same tension.
-
The use of naked conductors will be avoided.
-
It prohibit the use of switches of blades that properly are not protected.
- The
earth takings will leave more of 3m of wells and water obstacles.
-
A receiver fed by a transformer on 24V will not be placed to earth.

The very
dangerous pylons are place, that only must manipulate the experts.
2 - WORKS
WITHOUT TENSION
To isolate the part
in which one is going away to work of any possible feeding by means of the
opening of the apparatuses of block system next to the zone of work.
To block On guard
of opening each one of the block system apparatuses placing in its control a
signboard with the prohibition of maneuver.
To verify by means
of a checker the absence of electrical tension.
To signalize
suitably the prohibition to restitute electrical tension due to the work
accomplishment.
The service when
finalizing will not settle down the works without verifying that danger does not
exist some.
In the own place
of work it is recommended:
- Verification
of the absence of electrical tension.
-
In the case of aerial networks it will be come to the putting in short circuit.
-
To delimit the zone of work suitably signalizing it.

The rotating
lights can be a good signaling of the zone of work.
3 - WORKS
WITH TENSION
To be placed on
insulating objects (insulating carpets, sidewalks, stairs, etc.).
use insulating
helmets, gloves, protective goggles, isolated tools and appropriate clothes
without metallic accessories.
To previously
isolate the other conductors in tension, next to the work place, even the
neutral one.
When the work is
made to install an accountant with electrical tension, in addition to the
personal protective equipment, it is necessary to verify the correspondence of
the entrance tips and exit of each phase. Also it will be verified if the
installation of the subscriber is cortocircuitada, verifying if there is return
tension before connecting each new thread of exit.
|